Bearing Capacity Technical Guidance on the Geotechnical Information Website (2024)

Theoretical (Ultimate) and allowable bearing capacity can be assessed for the following:

  • Shallow Foundations
    • strip footings
    • square footings
    • circular footings
  • Deep foundations
    • end bearing
    • skin friction

For comprehensive examples of bearing capacity problems see:

  • Bearing Capacity Examples

    Allowable Bearing Capacity

    Qa = Qu Qa = Allowable bearing capacity (kN/m2) or (lb/ft2)
    F.S.

    Where:

    Qu = ultimate bearing capacity (kN/m2)or (lb/ft2) *See below for theory
    F.S. = Factor of Safety *See information on factor of safety

    Ultimate Bearing Capacity for Shallow Foundations

    Terzaghi Ultimate Bearing Capacity Theory

    Qu = c Nc + g D Nq + 0.5 g B Ng
    = Ultimate bearing capacity equation for shallow strip footings, (kN/m2)(lb/ft2)

    Qu = 1.3 c Nc + g D Nq + 0.4 g B Ng
    = Ultimate bearing capacity equation for shallow square footings, (kN/m2)(lb/ft2)

    Qu = 1.3 c Nc + g D Nq + 0.3 g B Ng
    = Ultimate bearing capacity equation for shallow circular footings, (kN/m2)(lb/ft2)

    Where:

    c = Cohesion of soil (kN/m2) (lb/ft2),
    g = effective unit weight of soil (kN/m3) (lb/ft3), *see note below
    D = depth of footing (m) (ft),
    B = width of footing (m) (ft),
    Nc=cotf(Nq – 1),*see typical bearing capacity factors
    Nq=e2(3p/4-f/2)tanf / [2 cos2(45+f/2)], *see typical bearing capacity factors
    Ng=(1/2) tanf(kp /cos2 f - 1), *see typical bearing capacity factors
    e = Napier's constant = 2.718...,
    kp = passive pressure coefficient, and
    f = angle of internal friction (degrees).

    Notes:
    Effective unit weight, g, is the unit weight of the soil for soils above the water table and capillary rise. For saturated soils, the effective unit weight is the unit weight of water, gw, 9.81 kN/m3 (62.4 lb/ft3), subtracted from the saturated unit weight of soil.Find more information in the foundations section.

    Meyerhof Bearing Capacity Theory Based on Standard Penetration Test Values

    Qu = 31.417(NB + ND) (kN/m2) (metric)

    Qu = NB + ND (tons/ft2) (standard)
    10 10

    For footing widths of 1.2 meters (4 feet) or less

    Qa = 11,970N (kN/m2) (metric)

    Qa = 1.25N (tons/ft2) (standard)
    10

    For footing widths of 3 meters (10 feet) or more

    Qa = 9,576N (kN/m2) (metric)

    Qa = N (tons/ft2) (standard)
    10

    Where:

    N= N value derived from Standard Penetration Test (SPT)
    D = depth of footing (m) (ft), and
    B = width of footing (m) (ft).

    Note: All Meyerhof equations are for foundations bearing on clean sands. The first equation is for ultimate bearing capacity, while the second two are factored within the equation in order to provide an allowable bearing capacity. Linear interpolation can be performed for footing widths between 1.2 meters (4 feet) and 3 meters (10 feet). Meyerhof equations are based on limiting total settlement to 25 cm (1 inch), and differential settlement to 19 cm (3/4 inch).

    Ultimate Bearing Capacity for Deep Foundations (Pile)

    Qult = Qp + Qf

    Where:

    Qult = Ultimate bearing capacity of pile, kN (lb)
    Qp = Theoretical bearing capacity for tip of foundation, or end bearing, kN (lb)
    Qf = Theoretical bearing capacity due to shaft friction, or adhesion betweenfoundation shaft and soil, kN (lb)

    End Bearing (Tip) Capacity of Pile Foundation

    Qp = Apqp

    Where:

    Qp = Theoretical bearing capacity for tip of foundation, or end bearing, kN (lb)
    Ap = Effective area of the tip of the pile, m2 (ft2)
    For a circular closed end pile or circular plugged pile; Ap = p(B/2)2m2 (ft2)
    qp = gDNq
    = Theoretical unit tip-bearing capacity for cohesionless and silt soils, kN/m2 (lb/ft2)
    qp = 9c
    = Theoretical unit tip-bearing capacity for cohesive soils, kN/m2 (lb/ft2)
    g = effective unit weight of soil, kN/m3 (lb/ft3), *See notes below
    D = Effective depth of pile, m (ft), where D < Dc,
    Nq = Bearing capacity factor for piles,
    c = cohesion of soil, kN/m2 (lb/ft2),
    B = diameter of pile, m (ft), and
    Dc = critical depth for piles in loose silts or sands m (ft).
    Dc= 10B, for loose silts and sands
    Dc= 15B, for medium dense silts and sands
    Dc= 20B, for dense silts and sands

    Skin (Shaft) Friction Capacity of Pile Foundation

    Qf = Afqf&nbspfor one hom*ogeneous layer of soil

    Qf = pSqfL for multi-layers of soil

    Where:

    Qf = Theoretical bearing capacity due to shaft friction, or adhesion betweenfoundation shaft and soil, kN (lb)
    Af = pL; Effective surface area of the pile shaft, m2 (ft2)
    qf = ks tan d= Theoretical unit friction capacity for cohesionless soils, kN/m2 (lb/ft2)
    qf = cA + ks tan d= Theoretical unit friction capacity for silts, kN/m2 (lb/ft2)
    qf = aSu = Theoretical unit friction capacity for cohesive soils, kN/m2 (lb/ft2)
    p = perimeter of pile cross-section, m (ft)
    for a circular pile; p = 2p(B/2)
    for a square pile; p = 4B
    L = Effective length of pile, m (ft) *See Notes below
    a = 1 - 0.1(Suc)2 = adhesion factor, kN/m2 (ksf), where Suc < 48 kN/m2 (1 ksf)
    a = 1 [0.9 + 0.3(Suc - 1)] kN/m2, (ksf) where Suc > 48 kN/m2, (1 ksf)
    Suc
    Suc = 2c = Unconfined compressive strength , kN/m2 (lb/ft2)
    cA = adhesion
    = c for rough concrete, rusty steel, corrugated metal
    0.8c < cA < c for smooth concrete
    0.5c < cA < 0.9c for clean steel
    c = cohesion of soil, kN/m2 (lb/ft2)
    d = external friction angleof soil and wall contact (deg)
    f= angle of internalfriction (deg)
    s = gD = effective overburden pressure, kN/m2, (lb/ft2)
    k = lateral earth pressure coefficientfor piles
    g = effective unit weight of soil, kN/m3 (lb/ft3) *See notes below
    B = diameter or width of pile, m (ft)
    D = Effective depth of pile, m (ft), where D < Dc
    Dc = critical depth for piles in loose silts or sands m (ft).
    Dc= 10B, for loose silts and sands
    Dc= 15B, for medium dense silts and sands
    Dc= 20B, for dense silts and sands
    S = summation of differing soil layers (i.e. a1 + a2 + .... + an)

    Notes: Determining effective length requires engineering judgment. The effective length can be the pile depth minus any disturbed surface soils, soft/ loose soils, or seasonal variation. The effective length may also be the length of a pile segment within a single soil layer of a multi layered soil. Effective unit weight, g, is the unit weight of the soil for soils above the water table and capillary rise. For saturated soils, the effective unit weight is the unit weight of water, gw, 9.81 kN/m3 (62.4 lb/ft3), subtracted from the saturated unit weight of soil.

    ************

    Meyerhof Method for Determining qp and qf in Sand

    Theoretical unit tip-bearing capacity for driven piles in sand, when D > 10:
    B
    qp = 4Nc tons/ft2standard

    Theoretical unit tip-bearing capacity for drilled piles in sand:

    qp = 1.2Nc tons/ft2standard

    Theoretical unit friction-bearing capacity for driven piles in sand:

    qf = Ntons/ft2 standard
    50

    Theoretical unit friction-bearing capacity for drilled piles in sand:

    qf = Ntons/ft2 standard
    100

    Where:

    D = pile embedment depth, ft
    B = pile diameter, ft
    Nc = Cn(N)
    Cn = 0.77 log 20
    s

    N = N-Value from SPT test
    s = gD = effective overburden stress at pile embedment depth, tons/ft2
    = (g - gw)D = effective stress if below water table, tons/ft2
    g = effective unit weight of soil, tons/ft3
    gw = 0.0312 tons/ft3 = unit weight of water

Examples for determining allowable bearing capacity

Example #1: Determine allowable bearing capacity and width for a shallow strip footing on cohesionless silty sand and gravel soil. Loose soils were encountered in the upper 0.6 m (2 feet) of building subgrade. Footing must withstand a 144 kN/m2 (3000 lb/ft2) building pressure.

Given

Solution

Try a minimal footing width, B = 0.3 m (B = 1 foot).

Use a factor of safety, F.S = 3. Three is typical for this type of application. Seefactor of safety for more information.

Determine bearing capacity factors Ng, Nc and Nq. See typical bearing capacity factors relating to the soils' angle of internal friction.

  • Ng = 22
  • Nc = 35.5
  • Nq = 23.2

Solve for ultimate bearing capacity,

Qu = c Nc + g D Nq + 0.5 g B Ng *strip footing eq.

Qu = 0(35.5) + 21 kN/m3(0.6m)(23.2) + 0.5(21 kN/m3)(0.3 m)(22)metric
Qu = 362 kN/m2

Qu = 0(35.5) + 132lbs/ft3(2ft)(23.2) + 0.5(132lbs/ft3)(1ft)(22)standard
Qu = 7577 lbs/ft2

Solve for allowable bearing capacity,

Qa = Qu
F.S.

Qa = 362 kN/m2 = 121 kN/m2 not o.k. metric
3
Qa = 7577lbs/ft2 = 2526 lbs/ft2 not o.k. standard
3

Since Qa < required 144 kN/m2 (3000 lbs/ft2) bearing pressure, increase footing width, B orfoundation depth, D to increase bearing capacity.

Try footing width, B = 0.61 m (B = 2 ft).

Qu = 0 + 21 kN/m3(0.61 m)(23.2) + 0.5(21 kN/m3)(0.61 m)(22)metric
Qu = 438 kN/m2

Qu = 0 + 132 lbs/ft3(2 ft)(23.2) + 0.5(132 lbs/ft3)(2 ft)(22)standard
Qu = 9029 lbs/ft2

Qa = 438 kN/m2 = 146 kN/m2Qa > 144 kN/m2 o.k. metric
3

Qa = 9029 lbs/ft2 = 3010 lbs/ft2Qa > 3000 lbs/ft2 o.k. standard
3

Conclusion

Footing shall be 0.61 meters (2 feet) wide at a depth of 0.61 meters (2 feet) below ground surface. Many engineers neglect the depth factor (i.e. D Nq = 0) for shallow foundations. This inherently increases the factor of safety. Some site conditions that may negatively effect the depth factor are foundations established at depths equal to or less than 0.3 meters (1 feet) below the ground surface, placement of foundations on fill, and disturbed/ fill soils located above or to the sides of foundations.

********************************

Example #2: Determine allowable bearing capacity of a shallow, 0.3 meter (12-inch) squareisolated footing bearing on saturated cohesive soil. The frost penetration depth is 0.61 meter (2 feet). Structural parameters require the foundation to withstand 4.4 kN (1000 lbs) of force on a 0.3 meter (12-inch) square column.

Given

  • bearing pressure from building column = 4.4 kN/ (0.3 m x 0.3 m) = 48.9 kN/m2

  • bearing pressure from building column = 1000 lbs/ (1 ft x 1 ft) = 1000 lbs/ft2

  • unit weight of saturated soil, gsat= 20.3 kN/m3 (129 lbs/ft3) *see typical g values

  • unit weight of water, gw= 9.81 kN/m3 (62.4 lbs/ft3) *constant

  • Cohesion, c = 21.1 kN/m2 (440 lbs/ft2) *from soil testing, see typicalc values

  • angle of Internal Friction, f = 0 degrees *from soil testing, see typicalf values

  • footing width, B = 0.3 m (1 ft)

Solution

Try a footing depth, D = 0.61 meters (2 feet), because foundation should be below frost depth.

Use a factor of safety, F.S = 3. Seefactor of safety for more information.

Determine bearing capacity factors Ng, Nc and Nq. See typical bearing capacity factors relating to the soils' angle of internal friction.

  • Ng = 0
  • Nc = 5.7
  • Nq = 1

Solve for ultimate bearing capacity,

Qu = 1.3c Nc + g D Nq + 0.4 g B Ng *square footing eq.

Qu =1.3(21.1kN/m2)5.7+(20.3kN/m3-9.81kN/m3)(0.61m)1+0.4(20.3kN/m3-9.81kN/m3)(0.3m)0
Qu = 163 kN/m2 metric

Qu = 1.3(440lbs/ft2)(5.7) + (129lbs/ft3 - 62.4lbs/ft3)(2ft)(1) + 0.4(129lbs/ft3 - 62.4lbs/ft3)(1ft)(0)
Qu = 3394 lbs/ft2 standard

Solve for allowable bearing capacity,

Qa = Qu
F.S.

Qa = 163 kN/m2 = 54 kN/m2 Qa > 48.9 kN/m2 o.k. metric
3
Qa = 3394lbs/ft2 = 1130 lbs/ft2 Qa > 1000 lbs/ft2 o.k. standard
3

Conclusion

The 0.3 meter (12-inch) isolated square footing shall be 0.61 meters (2 feet) below the ground surface.Other considerations may be required for foundations bearingon moisture sensitive clays, especially for lightly loaded structures such as in this example. Sensitive clays could expand and contract, which could cause structural damage. Clay used as bearing soils may require mitigation such as heavier loads, subgrade removal and replacement below the foundation, or moisture control within the subgrade.

********************************

Example #3: Determine allowable bearing capacity and width for a foundation using the Meyerhof Method. Soils consist of poorly graded sand. Footing must withstand a 144 kN/m2 (1.5 tons/ft2) building pressure.

Given

  • bearing pressure from building = 144 kN/m2 (1.5 tons/ft2)
  • N Value, N = 10 at 0.3 m (1 ft) depth *from SPT soil testing
  • N Value, N = 36 at 0.61 m (2 ft) depth*from SPT soil testing
  • N Value, N = 50 at 1.5 m (5 ft) depth *from SPT soil testing

Solution

Try a minimal footing width, B = 0.3 m (B = 1 foot) at a depth, D = 0.61 meter (2 feet). Footings for single family residences are typically 0.3m (1 ft) to 0.61m (2ft) wide. This depth was selected because soil density greatly increases (i.e. higher N-value) at a depth of 0.61 m (2 ft).

Use a factor of safety, F.S = 3. Three is typical for this type of application. Seefactor of safety for more information.

Solve for ultimate bearing capacity

Qu = 31.417(NB + ND) (kN/m2) (metric)

Qu = NB + ND (tons/ft2) (standard)
10 10

Qu = 31.417(36(0.3m) + 36(0.61m)) = 1029 kN/m2(metric)

Qu = 36(1 ft) + 36(2 ft)= 10.8 tons/ft2(standard)
10 10

Solve for allowable bearing capacity,

Qa = Qu
F.S
.

Qa = 1029 kN/m2 = 343 kN/m2 Qa > 144kN/m2o.k.(metric)
3
Qa = 10.8 tons/ft2 = 3.6 tons/ft2 Qa > 1.5tons/ft2o.k. (standard)
3

Conclusion

Footing shall be 0.3 meters (1 feet) wide at a depth of 0.61 meters (2 feet) below the ground surface. A footing width of only 0.3 m (1 ft) is most likely insufficient for the structural engineer when designing the footing with the building pressure in this problem.

********************************

Example #4: Determine allowable bearing capacity and diameter of a single driven pile. Pile must withstand a 66.7 kN (15 kips) vertical load.

Given

  • vertical column load = 66.7 kN (15 kips or 15,000 lb)
  • hom*ogeneous soils in upper 15.2 m (50 ft); silty soil
    • unit weight, g = 19.6 kN/m3 (125 lbs/ft3) *from soil testing, see typical g values
    • cohesion, c = 47.9 kN/m2 (1000 lb/ft2) *from soil testing, see typicalc values
    • angle of internal friction, f = 30 degrees *from soil testing, see typicalf values
  • Pile Information
    • driven
    • steel
    • plugged end

Solution

Try a pile depth, D = 1.5 meters (5 feet)
Try pile diameter, B = 0.61 m (2 ft)

Use a factor of safety, F.S = 3. Smaller factors of safety are sometimes used if piles are load tested, or the engineer has sufficient experience with the regional soils.

Determine ultimate end bearing of pile,

Qp = Apqp

Ap = p(B/2)2 = p(0.61m/2)2 = 0.292 m2 metric
Ap=p(B/2)2 = p(2ft/2)2 = 3.14 ft2 standard

qp = gDNq

g = 19.6 kN/m3 (125 lbs/ft3); given soil unit weight
f = 30 degrees; given soil angle of internal friction
B = 0.61 m (2 ft); trial pile width
D = 1.5 m (5 ft); trial depth, may need to increase or decrease depending on capacity
check to see if D < Dc
Dc = 15B = 9.2 m (30 ft); critical depth for medium dense silts.
If D > Dc, then use Dc
Nq = 25; Meyerhof bearing capacityfactor for driven piles, based onf

qp = 19.6 kN/m3(1.5 m)25 = 735 kN/m2 metric
qp = 125 lb/ft3(5 ft)25 = 15,625 lb/ft2 standard


Qp = Apqp = (0.292 m2)(735 kN/m2)= 214.6 kN metric
Qp = Apqp = (3.14 ft2)(15,625 lb/ft2)= 49,063 lb standard

Determine ultimate friction capacity of pile,

Qf = Afqf

Af = pL

p = 2p(0.61m/2) = 1.92 m metric
p = 2p(2 ft/2) = 6.28 ft standard
L = D = 1.5 m (5 ft); length and depth used interchangeably. check Dc as above

Af = 1.92 m(1.5 m) = 2.88 m2 metric
Af = 6.28 ft(5 ft) = 31.4 ft2 standard

qf = cA + ks tan d = cA + kgD tand

k = 0.5; lateral earth pressure coefficientfor piles, value chosen from Broms low density steel
g = 19.6 kN/m3 (125 lb/ft3); given effective soil unit weight. If water table, theng - gw
D = L = 1.5 m (5 ft); pile length. Check to see if D < Dc
Dc = 15B = 9.2 m (30 ft); critical depth for medium dense silts. If D > Dc, then use Dc
d = 20 deg; external friction angle, equation chosen from Broms steel piles
B = 0.61 m (2 ft); selected pile diameter
cA = 0.5c; for clean steel. See adhesion in pile theories above.
= 24 kN/m2 (500 lb/ft2)

qf = 24 kN/m2 + 0.5(19.6 kN/m3)(1.5m)tan 20 = 29.4 kN/m2 metric
qf = 500 lb/ft2 + 0.5(125 lb/ft3)(5ft)tan 20 = 614 lb/ft2standard

Qf = Afqf = 2.88 m2(29.4 kN/m2)= 84.7 kN metric
Qf = Afqf = 31.4 ft2(614 lb/ft2)= 19,280 lb standard

Determine ultimate pile capacity,

Qult = Qp + Qf

Qult = 214.6 kN + 84.7 kN= 299.3 kN metric
Qult = 49,063 lb + 19,280 lb = 68,343 lb standard

Solve for allowable bearing capacity,

Qa = Qult
F.S.

Qa = 299.3 kN = 99.8 kN; Qa > applied load (66.7 kN) o.k.metric
3
Qa = 68,343 lbs = 22,781 lbs Qa > applied load (15 kips) o.k. standard
3

Conclusion

A 0.61 m (2 ft) steel pile shall be plugged and driven 1.5 m (5 feet) below the ground surface. Many engineers neglect the skin friction within the upper 1 to 5 feet of subgrade due to seasonal variations or soil disturbance.Seasonal variations may include freeze/ thaw or effects from water. The end bearing alone (neglect skin friction) is sufficient for this case. Typical methods for increasing the pile capacity are increasing the pile diameter or increasing the embedment depth of the pile.

********************************

Example #5: Determine allowable bearing capacity and diameter of a single driven pile. Pile must withstand a 66.7 kN (15 kips) vertical load.

Given

  • vertical column load = 66.7 kN (15 kips or 15,000 lb)

  • upper 1.5 m (5 ft) of soil is a medium dense gravelly sand

    • unit weight, g = 19.6 kN/m3 (125 lbs/ft3) *from soil testing, see typical g values
    • cohesion, c = 0 *from soil testing, see typicalc values
    • angle of internal friction, f = 30 degrees *from soil testing, see typicalf values
  • soils below 1.5 m (5 ft) of soil is a stiff silty clay

    • unit weight, g = 18.9 kN/m3 (120 lbs/ft3)
    • cohesion, c = 47.9 kN/m2 (1000 lb/ft2)
    • angle of internal friction, f = 0 degrees
  • Pile Information

    • driven
    • wood
    • closed end

Solution

Try a pile depth, D = 2.4 meters (8 feet)
Try pile diameter, B = 0.61 m (2 ft)

Use a factor of safety, F.S = 3. Smaller factors of safety are sometimes used if piles are load tested, or the engineer has sufficient experience with the regional soils.

Determine ultimate end bearing of pile,

Qp = Apqp

Ap = p(B/2)2 = p(0.61m/2)2 = 0.292 m2 metric
Ap=p(B/2)2 = p(2ft/2)2 = 3.14 ft2 standard


qp = 9c = 9(47.9 kN/m2) = 431.1 kN/m2 metric
qp = 9c = 9(1000 lb/ft2) = 9000 lb/ft2 standard


Qp = Apqp = (0.292 m2)(431.1 kN/m2)= 125.9 kN metric
Qp = Apqp = (3.14 ft2)(9000 lb/ft2)= 28,260 lb standard

Determine ultimate friction capacity of pile,

Qf = pSqfL

p = 2p(0.61m/2) = 1.92 m metric
p = 2p(2 ft/2) = 6.28 ft standard

upper 1.5 m (5 ft) of soil

qfL = [ks tan d]L= [kgD tand]L

k = 1.5; lateral earth pressure coefficientfor piles, value chosen from Broms low density timber
g = 19.6 kN/m3 (125 lb/ft3); given effective soil unit weight. If water table, theng - gw
D = L = 1.5 m (5 ft); segment of pile within this soil strata. Check to see if D < Dc
Dc = 15B = 9.2 m (30 ft); critical depth for medium dense sands. This assumption is conservative, because the soil is gravelly, and this much soil unit weight for a sand would indicate dense soils. If D > Dc, then use Dc
d = f(2/3) = 20 deg; external friction angle, equation chosen from Broms timber piles
B = 0.61 m (2 ft); selected pile diameter
f = 30 deg; given soil angle of internal friction

qfL = [1.5(19.6 kN/m3)(1.5m)tan (20)]1.5 m = 24.1 kN/mmetric
qfL = [1.5(125 lb/ft3)(5ft)tan (20)]5 ft = 1706 lb/ftstandard

soils below 1.5 m (5 ft) of subgrade

qfL =aSu

Suc = 2c = 95.8 kN/m2 (2000 lb/ft2);unconfined compressive strength
c = 47.9 kN/m2 (1000 lb/ft2); cohesion from soil testing (given)
a =

1

[0.9 + 0.3(Suc - 1)] = 0.3; because Suc > 48 kN/m2, (1 ksf)
Suc
L = 0.91 m (3 ft); segment of pile within this soil strata

qfL = [0.3(95.8 kN/m2)]0.91 m = 26.2 kN/mmetric
qfL = [0.3(2000 lb/ft2)]3 ft = 1800 lb/ft standard

ultimate friction capacity of combined soil layers

Qf = pSqfL

Qf = 1.92 m(24.1 kN/m + 26.2 kN/m) = 96.6 kN metric
Qf = 6.28 ft(1706 lb/ft + 1800 lb/ft) = 22,018 lb standard

Determine ultimate pile capacity,

Qult = Qp + Qf

Qult = 125.9 kN + 96.6 kN= 222.5 kN metric
Qult = 28,260 lb + 22,018 lb = 50,278 lb standard

Solve for allowable bearing capacity,

Qa = Qult
F.S.

Qa = 222.5 kN = 74.2 kN; Qa > applied load (66.7 kN) o.k.metric
3
Qa = 50,275 lbs = 16,758 lbs Qa > applied load (15 kips) o.k. standard
3

Conclusion

Wood pile shall be driven 8 feet below the ground surface. Many engineers neglect the skin friction within the upper 1 to 5 feet of subgrade due to seasonal variations or soil disturbance.Seasonal variations may include freeze/ thaw or effects from water. Notice how the soil properties within the pile tip location is used in the endbearing calculations. End bearing should also consider the soil layer(s) directly beneath this layer. Engineering judgment or a change in design is warranted if subsequent soil layers are weaker than the soils within the vicinity of the pile tip. Typical methods for increasing the pile capacity are increasing the pile diameter or increasing the embedment depth of the pile.

********************************

Please look at additional information and related sources for Bearing Capacityin the publications or software links.Or, post a question in the Geotechnical Forum.

If you found this website useful, then Tell a friend!

Bearing Capacity Technical Guidance on the Geotechnical Information Website (2024)
Top Articles
Working with text files in Python - Quick start
I'm 65 With $1 Million in a 401(k) and $2,500 Social Security Benefit. Can I Retire?
Why Are Fuel Leaks A Problem Aceable
Matgyn
NYT Mini Crossword today: puzzle answers for Tuesday, September 17 | Digital Trends
Craigslist Free En Dallas Tx
Inducement Small Bribe
Frank Lloyd Wright, born 150 years ago, still fascinates
Mackenzie Rosman Leaked
Chase Bank Operating Hours
Es.cvs.com/Otchs/Devoted
Yi Asian Chinese Union
Parks in Wien gesperrt
Lycoming County Docket Sheets
Hello Alice Business Credit Card Limit Hard Pull
Uvalde Topic
Maxpreps Field Hockey
Inside California's brutal underground market for puppies: Neglected dogs, deceived owners, big profits
Cbs Trade Value Chart Fantasy Football
Conan Exiles Thrall Master Build: Best Attributes, Armor, Skills, More
Operation Cleanup Schedule Fresno Ca
Carolina Aguilar Facebook
Mzinchaleft
CANNABIS ONLINE DISPENSARY Promo Code — $100 Off 2024
Apply for a credit card
Erica Banks Net Worth | Boyfriend
Sea To Dallas Google Flights
Tu Pulga Online Utah
Certain Red Dye Nyt Crossword
Directions To Cvs Pharmacy
11 Ways to Sell a Car on Craigslist - wikiHow
Southland Goldendoodles
eugene bicycles - craigslist
Znamy dalsze plany Magdaleny Fręch. Nie będzie nawet chwili przerwy
Dashboard Unt
Dal Tadka Recipe - Punjabi Dhaba Style
Bend Missed Connections
Nurtsug
Home Auctions - Real Estate Auctions
Rock Salt Font Free by Sideshow » Font Squirrel
15 Downer Way, Crosswicks, NJ 08515 - MLS NJBL2072416 - Coldwell Banker
Craigslist Lakeside Az
Simnet Jwu
Walmart Pharmacy Hours: What Time Does The Pharmacy Open and Close?
Below Five Store Near Me
Streameast Io Soccer
855-539-4712
De boeken van Val McDermid op volgorde
Msatlantathickdream
Sam's Club Fountain Valley Gas Prices
Factorio Green Circuit Setup
Cheryl Mchenry Retirement
Latest Posts
Article information

Author: Madonna Wisozk

Last Updated:

Views: 6133

Rating: 4.8 / 5 (48 voted)

Reviews: 87% of readers found this page helpful

Author information

Name: Madonna Wisozk

Birthday: 2001-02-23

Address: 656 Gerhold Summit, Sidneyberg, FL 78179-2512

Phone: +6742282696652

Job: Customer Banking Liaison

Hobby: Flower arranging, Yo-yoing, Tai chi, Rowing, Macrame, Urban exploration, Knife making

Introduction: My name is Madonna Wisozk, I am a attractive, healthy, thoughtful, faithful, open, vivacious, zany person who loves writing and wants to share my knowledge and understanding with you.